Visible to Intel only — GUID: sam1405085364607
Ixiasoft
System Setup
The bus transmission line is assumed to have the following characteristics:
- A stripline
- Characteristic impedance of 50 Ω
- Characteristic capacitance of 3.6 pF per inch
- Length of 10 inches
- Bus differential characteristic impedance of approximately 100 Ω
- Spacing between each transceiver of 1 inch
- Bus terminated at both ends with termination resistor RT
In the example shown in the preceding figure, the fail-safe biasing resistors of 130 kΩ and 100 kΩ pulls the bus to a known state when all the drivers are tri-stated, removed, or powered off.
To prevent excessive loading to the driver and waveform distortion, the magnitude of the fail-safe resistors must be one or two orders higher than RT. To prevent a large common-mode shift from occurring between the active and tri-state bus conditions, the mid-point of the fail-safe bias must be close to the offset voltage of the driver (+1.25 V). You can power up the bus with the common power supplies (VCC).
Cyclone® III, Cyclone® IV, and Intel® Cyclone® 10 LP BLVDS transceivers are assumed to have the following characteristics:
- Default drive strength of 12 mA
- Slow slew rate settings by default
- Pin capacitance of each transceiver of 6 pF
- Stub on each BLVDS transceiver is a 1-inch microstrip of characteristic impedance of 50 Ω and characteristic capacitance of 3 pF per inch
- Capacitance of the connection (connector, pad, and via in PCB) of each transceiver to the bus is assumed to be 2 pF
- Total capacitance of each load is approximately 11 pF
For 1-inch load spacing, the distributed capacitance is equal to 11 pF per inch. To reduce reflection caused by the stubs, and also to attenuate the signals coming out of the driver, an impedance matching 50 Ω resistor RS is placed at the output of each transceiver.