Article ID: 000087466 Content Type: Connectivity Last Reviewed: 12/12/2024

Real Time Operating System (RTOS) Unable to Communicate with Devices in the Network with Intel® Edge Controls for Industrial (Intel® ECI)

BUILT IN - ARTICLE INTRO SECOND COMPONENT
Summary

Quick steps to configure network access for Real Time Operating System (RTOS) with Intel® Edge Controls for Industrial (Intel® ECI).

Description
  • Added Real Time Operating System (RTOS) system to network
  • System is not able to communicate to other device on the network
Resolution

Configure the Real Time Operating (RTOS) system to access the network by passthrough on a PCI Network Controller.

  1. Check PCI device vendor and device ID want to passthrough to RTOS by running the following command.

    lspci -n command.

  2. Edit /boot/rth/Linux_Linux64.txt

    [/PCI/1]
    "OS" = uint32: 1
    "vendor_ID" = uint32: 0x8086
    "device_ID" = uint32: 0x1533
    "interrupt_mode" = uint32: 2

Related Products

This article applies to 1 products