Chassis Compatibility for the Intel® Server Board S2600CW Family
This page lists the tested chassis for the Intel® Server Board S2600CW Family and consists of two sections:
Tested Intel® Server Chassis list
Reference chassis list
Tested Intel® Server Chassis list
Intel® Server Chassis P4304XXMFEN2 |
|
Intel® Server Chassis P4304XXMUXX |
|
The reference chassis list includes third-party chassis tested for the Intel® Server Board S2600CW Family. Chassis are tested to see if they provide adequate airflow to meet individual manufacturer temperature specifications.
Vendor | Model | Chassis type | Power supply | Unpackage shock test | Thermal test level | Driver support |
Chenbro* | RM13604T2-CW | Rack | H/S | Pass with 25G | 1 | A |
Chenbro* | RM23612M2-R875CW | Rack | H/S | Pass with 25G | 1 | A |
Chenbro* | RM31616E2-R875CW | Rack | H/S | Pass with 25G | 1 | A |
Chenbro* | RM41824E2-R875CW | Rack | H/S | Pass with 25G | 1 | A |
Chenbro* | SR112 | Pedestal | Single | Pass with 25G | 1 | A |
In-win* | PV689 | Pedestal | Single | Pass with 25G | 1 | A |
In-win* | PP689 | Pedestal | Single | Pass with 25G | 1 | A |
In-win* | RS11002 | Rack | H/S | Pass with 25G | 3 | A |
In-win* | RS212 | Rack | H/S | Pass with 25G | 1 | A |
CI-Design* | NSR224 | Rack | H/S | Pass with 25G | 1 | A |
CI-Design* | NSR316 | Rack | H/S | Pass with 25G | 1 | A |
AIC* | RSC-2EH | Rack | H/S | Pass with 25G | 1 | A |
AIC* | RSC-2ET | Rack | H/S | Pass with 25G | 1 | A |
AIC* | RSC-3ET | Rack | H/S | Pass with 25G | 1 | A |
AIC* | RSC-4EG | Rack | H/S | Pass with 25G | 2 | A |
Z-Micro* | ZX22AC-S2600C-020 | Rack | H/S | Pass with 25G | 3 | A |
Note | Results are posted when new chassis are tested. |
Power supply
- H/S = Hot Swap Redundant
- Single = Single power supply
Thermal test level
Thermal testing is done on Intel® Server Boards for all listed third-party reference chassis. The Intel® Server Board is configured to use a generic fan control scheme that runs all attached system fans at 100-percent pulse width modulation (PWM). The generic fan control scheme is set by selecting the OTHER CHASSIS option using the FRUSDR Configuration Utility.
Results are not guaranteed if the fan control PWM rate is reduced or changed from the tested configuration. If you change the PWM rate, you are responsible for all required thermal validation to make sure that the system configurations meet the maximum thermal limits.
The table lists the chassis configuration summary and the highest level of Intel thermal testing achieved.
Level | Board revision | Processor | Maximum speed | CPU TDP | Manufacturing process technology | Number of drives | Ambient temperature |
1 | All | Intel® Xeon® Processor E5-2600 Sequence | 2.6 GHz | 145W | 22 nm | 1 | 35° Celsius |
2 | All | Intel® Xeon® Processor E5-2600 Sequence | 2.6 GHz | 145W | 22 nm | 1 | 30° Celsius |
3 | All | Intel® Xeon® Processor E5-2600 Sequence | 2.6 GHz | 120W | 22 nm | 1 | 35° Celsius |
Related topic |
Intel® Product Compatibility Tool for Operating System and Chassis |